Lift Manager v1.0
Version Info
- Add 'Priority Index' configuration parameter.
- Add status parameters to show the actual load ratio and Plunger Lift control state.
Group 'Plunger Coordination'
Coordinate plunger lift applications
This is a configuration group that has 139 parameters.
| Parameter | Tag Name | ID | Value Type | Tag Value Type | IO Type | Default Value | Limits | Default Units | Allowed Units | Description | Sync Enabled | Sync Default | Export Enabled | Publish MQTT Enabled | Subscribe MQTT Enabled | Show in Manager Enabled | Modbus Server Enabled | gRPC Read Enabled | gRPC Write Enabled |
| Enable Plunger Coordination | enPlCoord | 1114112 | bool | i | True | min:False;max:True; | Global enable for plunger lift coordination features. When this value is true to the application will coordinate plunger lift applications and prevent more than the configured number of applications from lifting at the same time. When false, this app will not manage any plunger lift applications. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Coordination Metric | plCoordMetric | 1114113 | i32 | i | 0:Priority | 0:Priority; 1:High Load Ratio; 2:Low Load Ratio; 3:Round Robin; | Select the metric to use to determine which wells are allowed to flow first. 'Priority' always selects the well with the lowest value of 'Priority Index'. 'High Load Ratio' selects the well with the highest load ratio. 'Low Load Ratio' selects the well with the lowest load ratio. 'Round Robin' selects the next enabled well where wells are sorted from the lowest value of 'Priority Index' to the highest. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Max Lift Count | maxLiftCount | 1114120 | i16 | i | 1 | min:1;max:16; | The number of wells that can simultaneously lift at the same time. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Enable Well Coordination 01 | enWellCoord_001 | 1116262 | bool | i | False | min:False;max:True; | Whether to include this configuration in the group of plunger lift applications that are coordinated. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Priority Index 01 | priorityIdx_001 | 1116270 | i16 | i | 100 | min:0;max:32767; | Set the priority of this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Remote Well Location 01 | locationRemote_001 | 1116263 | bool | i | False | min:False;max:True; | Set this value when the plunger lift application to be coordinated exists on a different controller or in a different PLC Shift runtime. When set, this application will coordinate the plunger lift application through the use of tags that are mapped through the PLC. When false, this application will coordinate the plunger lift application through an internal mechanism and the application must be in the same PLC Shift runtime. | ✓ | ✓ | ✓ | |||||||||
| Plunger Lift Application Prefix 01 | prefixPl_001 | 1116264 | string | i | PL01_ | minChars:2;maxChars:12; spaces:False; lettersNumbersOnly:True; | The configured tag name prefix for the plunger lift application. | ✓ | ✓ | ||||||||||
| Control State Tag Name 01 | controlStateTgNm_001 | 1116265 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Control State' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Inhibit Open Valve Tag Name 01 | inhibitOpenTgNm_001 | 1116266 | string | bool | o | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Inhibit Open Valve' control parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Load Ratio Tag Name 01 | loadRatioTgNm_001 | 1116267 | string | double | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Load Ratio' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Exec Count Tag Name 01 | execCountTgNm_001 | 1116269 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Execution Count' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Enable Well Coordination 02 | enWellCoord_002 | 1116362 | bool | i | False | min:False;max:True; | Whether to include this configuration in the group of plunger lift applications that are coordinated. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Priority Index 02 | priorityIdx_002 | 1116370 | i16 | i | 100 | min:0;max:32767; | Set the priority of this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Remote Well Location 02 | locationRemote_002 | 1116363 | bool | i | False | min:False;max:True; | Set this value when the plunger lift application to be coordinated exists on a different controller or in a different PLC Shift runtime. When set, this application will coordinate the plunger lift application through the use of tags that are mapped through the PLC. When false, this application will coordinate the plunger lift application through an internal mechanism and the application must be in the same PLC Shift runtime. | ✓ | ✓ | ✓ | |||||||||
| Plunger Lift Application Prefix 02 | prefixPl_002 | 1116364 | string | i | PL01_ | minChars:2;maxChars:12; spaces:False; lettersNumbersOnly:True; | The configured tag name prefix for the plunger lift application. | ✓ | ✓ | ||||||||||
| Control State Tag Name 02 | controlStateTgNm_002 | 1116365 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Control State' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Inhibit Open Valve Tag Name 02 | inhibitOpenTgNm_002 | 1116366 | string | bool | o | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Inhibit Open Valve' control parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Load Ratio Tag Name 02 | loadRatioTgNm_002 | 1116367 | string | double | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Load Ratio' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Exec Count Tag Name 02 | execCountTgNm_002 | 1116369 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Execution Count' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Enable Well Coordination 03 | enWellCoord_003 | 1116462 | bool | i | False | min:False;max:True; | Whether to include this configuration in the group of plunger lift applications that are coordinated. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Priority Index 03 | priorityIdx_003 | 1116470 | i16 | i | 100 | min:0;max:32767; | Set the priority of this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Remote Well Location 03 | locationRemote_003 | 1116463 | bool | i | False | min:False;max:True; | Set this value when the plunger lift application to be coordinated exists on a different controller or in a different PLC Shift runtime. When set, this application will coordinate the plunger lift application through the use of tags that are mapped through the PLC. When false, this application will coordinate the plunger lift application through an internal mechanism and the application must be in the same PLC Shift runtime. | ✓ | ✓ | ✓ | |||||||||
| Plunger Lift Application Prefix 03 | prefixPl_003 | 1116464 | string | i | PL01_ | minChars:2;maxChars:12; spaces:False; lettersNumbersOnly:True; | The configured tag name prefix for the plunger lift application. | ✓ | ✓ | ||||||||||
| Control State Tag Name 03 | controlStateTgNm_003 | 1116465 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Control State' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Inhibit Open Valve Tag Name 03 | inhibitOpenTgNm_003 | 1116466 | string | bool | o | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Inhibit Open Valve' control parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Load Ratio Tag Name 03 | loadRatioTgNm_003 | 1116467 | string | double | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Load Ratio' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Exec Count Tag Name 03 | execCountTgNm_003 | 1116469 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Execution Count' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Enable Well Coordination 04 | enWellCoord_004 | 1116562 | bool | i | False | min:False;max:True; | Whether to include this configuration in the group of plunger lift applications that are coordinated. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Priority Index 04 | priorityIdx_004 | 1116570 | i16 | i | 100 | min:0;max:32767; | Set the priority of this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Remote Well Location 04 | locationRemote_004 | 1116563 | bool | i | False | min:False;max:True; | Set this value when the plunger lift application to be coordinated exists on a different controller or in a different PLC Shift runtime. When set, this application will coordinate the plunger lift application through the use of tags that are mapped through the PLC. When false, this application will coordinate the plunger lift application through an internal mechanism and the application must be in the same PLC Shift runtime. | ✓ | ✓ | ✓ | |||||||||
| Plunger Lift Application Prefix 04 | prefixPl_004 | 1116564 | string | i | PL01_ | minChars:2;maxChars:12; spaces:False; lettersNumbersOnly:True; | The configured tag name prefix for the plunger lift application. | ✓ | ✓ | ||||||||||
| Control State Tag Name 04 | controlStateTgNm_004 | 1116565 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Control State' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Inhibit Open Valve Tag Name 04 | inhibitOpenTgNm_004 | 1116566 | string | bool | o | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Inhibit Open Valve' control parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Load Ratio Tag Name 04 | loadRatioTgNm_004 | 1116567 | string | double | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Load Ratio' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Exec Count Tag Name 04 | execCountTgNm_004 | 1116569 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Execution Count' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Enable Well Coordination 05 | enWellCoord_005 | 1116662 | bool | i | False | min:False;max:True; | Whether to include this configuration in the group of plunger lift applications that are coordinated. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Priority Index 05 | priorityIdx_005 | 1116670 | i16 | i | 100 | min:0;max:32767; | Set the priority of this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Remote Well Location 05 | locationRemote_005 | 1116663 | bool | i | False | min:False;max:True; | Set this value when the plunger lift application to be coordinated exists on a different controller or in a different PLC Shift runtime. When set, this application will coordinate the plunger lift application through the use of tags that are mapped through the PLC. When false, this application will coordinate the plunger lift application through an internal mechanism and the application must be in the same PLC Shift runtime. | ✓ | ✓ | ✓ | |||||||||
| Plunger Lift Application Prefix 05 | prefixPl_005 | 1116664 | string | i | PL01_ | minChars:2;maxChars:12; spaces:False; lettersNumbersOnly:True; | The configured tag name prefix for the plunger lift application. | ✓ | ✓ | ||||||||||
| Control State Tag Name 05 | controlStateTgNm_005 | 1116665 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Control State' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Inhibit Open Valve Tag Name 05 | inhibitOpenTgNm_005 | 1116666 | string | bool | o | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Inhibit Open Valve' control parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Load Ratio Tag Name 05 | loadRatioTgNm_005 | 1116667 | string | double | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Load Ratio' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Exec Count Tag Name 05 | execCountTgNm_005 | 1116669 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Execution Count' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Enable Well Coordination 06 | enWellCoord_006 | 1116762 | bool | i | False | min:False;max:True; | Whether to include this configuration in the group of plunger lift applications that are coordinated. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Priority Index 06 | priorityIdx_006 | 1116770 | i16 | i | 100 | min:0;max:32767; | Set the priority of this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Remote Well Location 06 | locationRemote_006 | 1116763 | bool | i | False | min:False;max:True; | Set this value when the plunger lift application to be coordinated exists on a different controller or in a different PLC Shift runtime. When set, this application will coordinate the plunger lift application through the use of tags that are mapped through the PLC. When false, this application will coordinate the plunger lift application through an internal mechanism and the application must be in the same PLC Shift runtime. | ✓ | ✓ | ✓ | |||||||||
| Plunger Lift Application Prefix 06 | prefixPl_006 | 1116764 | string | i | PL01_ | minChars:2;maxChars:12; spaces:False; lettersNumbersOnly:True; | The configured tag name prefix for the plunger lift application. | ✓ | ✓ | ||||||||||
| Control State Tag Name 06 | controlStateTgNm_006 | 1116765 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Control State' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Inhibit Open Valve Tag Name 06 | inhibitOpenTgNm_006 | 1116766 | string | bool | o | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Inhibit Open Valve' control parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Load Ratio Tag Name 06 | loadRatioTgNm_006 | 1116767 | string | double | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Load Ratio' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Exec Count Tag Name 06 | execCountTgNm_006 | 1116769 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Execution Count' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Enable Well Coordination 07 | enWellCoord_007 | 1116862 | bool | i | False | min:False;max:True; | Whether to include this configuration in the group of plunger lift applications that are coordinated. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Priority Index 07 | priorityIdx_007 | 1116870 | i16 | i | 100 | min:0;max:32767; | Set the priority of this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Remote Well Location 07 | locationRemote_007 | 1116863 | bool | i | False | min:False;max:True; | Set this value when the plunger lift application to be coordinated exists on a different controller or in a different PLC Shift runtime. When set, this application will coordinate the plunger lift application through the use of tags that are mapped through the PLC. When false, this application will coordinate the plunger lift application through an internal mechanism and the application must be in the same PLC Shift runtime. | ✓ | ✓ | ✓ | |||||||||
| Plunger Lift Application Prefix 07 | prefixPl_007 | 1116864 | string | i | PL01_ | minChars:2;maxChars:12; spaces:False; lettersNumbersOnly:True; | The configured tag name prefix for the plunger lift application. | ✓ | ✓ | ||||||||||
| Control State Tag Name 07 | controlStateTgNm_007 | 1116865 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Control State' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Inhibit Open Valve Tag Name 07 | inhibitOpenTgNm_007 | 1116866 | string | bool | o | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Inhibit Open Valve' control parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Load Ratio Tag Name 07 | loadRatioTgNm_007 | 1116867 | string | double | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Load Ratio' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Exec Count Tag Name 07 | execCountTgNm_007 | 1116869 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Execution Count' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Enable Well Coordination 08 | enWellCoord_008 | 1116962 | bool | i | False | min:False;max:True; | Whether to include this configuration in the group of plunger lift applications that are coordinated. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Priority Index 08 | priorityIdx_008 | 1116970 | i16 | i | 100 | min:0;max:32767; | Set the priority of this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Remote Well Location 08 | locationRemote_008 | 1116963 | bool | i | False | min:False;max:True; | Set this value when the plunger lift application to be coordinated exists on a different controller or in a different PLC Shift runtime. When set, this application will coordinate the plunger lift application through the use of tags that are mapped through the PLC. When false, this application will coordinate the plunger lift application through an internal mechanism and the application must be in the same PLC Shift runtime. | ✓ | ✓ | ✓ | |||||||||
| Plunger Lift Application Prefix 08 | prefixPl_008 | 1116964 | string | i | PL01_ | minChars:2;maxChars:12; spaces:False; lettersNumbersOnly:True; | The configured tag name prefix for the plunger lift application. | ✓ | ✓ | ||||||||||
| Control State Tag Name 08 | controlStateTgNm_008 | 1116965 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Control State' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Inhibit Open Valve Tag Name 08 | inhibitOpenTgNm_008 | 1116966 | string | bool | o | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Inhibit Open Valve' control parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Load Ratio Tag Name 08 | loadRatioTgNm_008 | 1116967 | string | double | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Load Ratio' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Exec Count Tag Name 08 | execCountTgNm_008 | 1116969 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Execution Count' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Enable Well Coordination 09 | enWellCoord_009 | 1117062 | bool | i | False | min:False;max:True; | Whether to include this configuration in the group of plunger lift applications that are coordinated. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Priority Index 09 | priorityIdx_009 | 1117070 | i16 | i | 100 | min:0;max:32767; | Set the priority of this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Remote Well Location 09 | locationRemote_009 | 1117063 | bool | i | False | min:False;max:True; | Set this value when the plunger lift application to be coordinated exists on a different controller or in a different PLC Shift runtime. When set, this application will coordinate the plunger lift application through the use of tags that are mapped through the PLC. When false, this application will coordinate the plunger lift application through an internal mechanism and the application must be in the same PLC Shift runtime. | ✓ | ✓ | ✓ | |||||||||
| Plunger Lift Application Prefix 09 | prefixPl_009 | 1117064 | string | i | PL01_ | minChars:2;maxChars:12; spaces:False; lettersNumbersOnly:True; | The configured tag name prefix for the plunger lift application. | ✓ | ✓ | ||||||||||
| Control State Tag Name 09 | controlStateTgNm_009 | 1117065 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Control State' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Inhibit Open Valve Tag Name 09 | inhibitOpenTgNm_009 | 1117066 | string | bool | o | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Inhibit Open Valve' control parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Load Ratio Tag Name 09 | loadRatioTgNm_009 | 1117067 | string | double | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Load Ratio' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Exec Count Tag Name 09 | execCountTgNm_009 | 1117069 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Execution Count' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Enable Well Coordination 10 | enWellCoord_010 | 1117162 | bool | i | False | min:False;max:True; | Whether to include this configuration in the group of plunger lift applications that are coordinated. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Priority Index 10 | priorityIdx_010 | 1117170 | i16 | i | 100 | min:0;max:32767; | Set the priority of this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Remote Well Location 10 | locationRemote_010 | 1117163 | bool | i | False | min:False;max:True; | Set this value when the plunger lift application to be coordinated exists on a different controller or in a different PLC Shift runtime. When set, this application will coordinate the plunger lift application through the use of tags that are mapped through the PLC. When false, this application will coordinate the plunger lift application through an internal mechanism and the application must be in the same PLC Shift runtime. | ✓ | ✓ | ✓ | |||||||||
| Plunger Lift Application Prefix 10 | prefixPl_010 | 1117164 | string | i | PL01_ | minChars:2;maxChars:12; spaces:False; lettersNumbersOnly:True; | The configured tag name prefix for the plunger lift application. | ✓ | ✓ | ||||||||||
| Control State Tag Name 10 | controlStateTgNm_010 | 1117165 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Control State' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Inhibit Open Valve Tag Name 10 | inhibitOpenTgNm_010 | 1117166 | string | bool | o | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Inhibit Open Valve' control parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Load Ratio Tag Name 10 | loadRatioTgNm_010 | 1117167 | string | double | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Load Ratio' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Exec Count Tag Name 10 | execCountTgNm_010 | 1117169 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Execution Count' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Enable Well Coordination 11 | enWellCoord_011 | 1117262 | bool | i | False | min:False;max:True; | Whether to include this configuration in the group of plunger lift applications that are coordinated. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Priority Index 11 | priorityIdx_011 | 1117270 | i16 | i | 100 | min:0;max:32767; | Set the priority of this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Remote Well Location 11 | locationRemote_011 | 1117263 | bool | i | False | min:False;max:True; | Set this value when the plunger lift application to be coordinated exists on a different controller or in a different PLC Shift runtime. When set, this application will coordinate the plunger lift application through the use of tags that are mapped through the PLC. When false, this application will coordinate the plunger lift application through an internal mechanism and the application must be in the same PLC Shift runtime. | ✓ | ✓ | ✓ | |||||||||
| Plunger Lift Application Prefix 11 | prefixPl_011 | 1117264 | string | i | PL01_ | minChars:2;maxChars:12; spaces:False; lettersNumbersOnly:True; | The configured tag name prefix for the plunger lift application. | ✓ | ✓ | ||||||||||
| Control State Tag Name 11 | controlStateTgNm_011 | 1117265 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Control State' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Inhibit Open Valve Tag Name 11 | inhibitOpenTgNm_011 | 1117266 | string | bool | o | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Inhibit Open Valve' control parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Load Ratio Tag Name 11 | loadRatioTgNm_011 | 1117267 | string | double | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Load Ratio' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Exec Count Tag Name 11 | execCountTgNm_011 | 1117269 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Execution Count' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Enable Well Coordination 12 | enWellCoord_012 | 1117362 | bool | i | False | min:False;max:True; | Whether to include this configuration in the group of plunger lift applications that are coordinated. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Priority Index 12 | priorityIdx_012 | 1117370 | i16 | i | 100 | min:0;max:32767; | Set the priority of this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Remote Well Location 12 | locationRemote_012 | 1117363 | bool | i | False | min:False;max:True; | Set this value when the plunger lift application to be coordinated exists on a different controller or in a different PLC Shift runtime. When set, this application will coordinate the plunger lift application through the use of tags that are mapped through the PLC. When false, this application will coordinate the plunger lift application through an internal mechanism and the application must be in the same PLC Shift runtime. | ✓ | ✓ | ✓ | |||||||||
| Plunger Lift Application Prefix 12 | prefixPl_012 | 1117364 | string | i | PL01_ | minChars:2;maxChars:12; spaces:False; lettersNumbersOnly:True; | The configured tag name prefix for the plunger lift application. | ✓ | ✓ | ||||||||||
| Control State Tag Name 12 | controlStateTgNm_012 | 1117365 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Control State' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Inhibit Open Valve Tag Name 12 | inhibitOpenTgNm_012 | 1117366 | string | bool | o | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Inhibit Open Valve' control parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Load Ratio Tag Name 12 | loadRatioTgNm_012 | 1117367 | string | double | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Load Ratio' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Exec Count Tag Name 12 | execCountTgNm_012 | 1117369 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Execution Count' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Enable Well Coordination 13 | enWellCoord_013 | 1117462 | bool | i | False | min:False;max:True; | Whether to include this configuration in the group of plunger lift applications that are coordinated. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Priority Index 13 | priorityIdx_013 | 1117470 | i16 | i | 100 | min:0;max:32767; | Set the priority of this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Remote Well Location 13 | locationRemote_013 | 1117463 | bool | i | False | min:False;max:True; | Set this value when the plunger lift application to be coordinated exists on a different controller or in a different PLC Shift runtime. When set, this application will coordinate the plunger lift application through the use of tags that are mapped through the PLC. When false, this application will coordinate the plunger lift application through an internal mechanism and the application must be in the same PLC Shift runtime. | ✓ | ✓ | ✓ | |||||||||
| Plunger Lift Application Prefix 13 | prefixPl_013 | 1117464 | string | i | PL01_ | minChars:2;maxChars:12; spaces:False; lettersNumbersOnly:True; | The configured tag name prefix for the plunger lift application. | ✓ | ✓ | ||||||||||
| Control State Tag Name 13 | controlStateTgNm_013 | 1117465 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Control State' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Inhibit Open Valve Tag Name 13 | inhibitOpenTgNm_013 | 1117466 | string | bool | o | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Inhibit Open Valve' control parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Load Ratio Tag Name 13 | loadRatioTgNm_013 | 1117467 | string | double | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Load Ratio' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Exec Count Tag Name 13 | execCountTgNm_013 | 1117469 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Execution Count' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Enable Well Coordination 14 | enWellCoord_014 | 1117562 | bool | i | False | min:False;max:True; | Whether to include this configuration in the group of plunger lift applications that are coordinated. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Priority Index 14 | priorityIdx_014 | 1117570 | i16 | i | 100 | min:0;max:32767; | Set the priority of this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Remote Well Location 14 | locationRemote_014 | 1117563 | bool | i | False | min:False;max:True; | Set this value when the plunger lift application to be coordinated exists on a different controller or in a different PLC Shift runtime. When set, this application will coordinate the plunger lift application through the use of tags that are mapped through the PLC. When false, this application will coordinate the plunger lift application through an internal mechanism and the application must be in the same PLC Shift runtime. | ✓ | ✓ | ✓ | |||||||||
| Plunger Lift Application Prefix 14 | prefixPl_014 | 1117564 | string | i | PL01_ | minChars:2;maxChars:12; spaces:False; lettersNumbersOnly:True; | The configured tag name prefix for the plunger lift application. | ✓ | ✓ | ||||||||||
| Control State Tag Name 14 | controlStateTgNm_014 | 1117565 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Control State' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Inhibit Open Valve Tag Name 14 | inhibitOpenTgNm_014 | 1117566 | string | bool | o | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Inhibit Open Valve' control parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Load Ratio Tag Name 14 | loadRatioTgNm_014 | 1117567 | string | double | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Load Ratio' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Exec Count Tag Name 14 | execCountTgNm_014 | 1117569 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Execution Count' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Enable Well Coordination 15 | enWellCoord_015 | 1117662 | bool | i | False | min:False;max:True; | Whether to include this configuration in the group of plunger lift applications that are coordinated. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Priority Index 15 | priorityIdx_015 | 1117670 | i16 | i | 100 | min:0;max:32767; | Set the priority of this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Remote Well Location 15 | locationRemote_015 | 1117663 | bool | i | False | min:False;max:True; | Set this value when the plunger lift application to be coordinated exists on a different controller or in a different PLC Shift runtime. When set, this application will coordinate the plunger lift application through the use of tags that are mapped through the PLC. When false, this application will coordinate the plunger lift application through an internal mechanism and the application must be in the same PLC Shift runtime. | ✓ | ✓ | ✓ | |||||||||
| Plunger Lift Application Prefix 15 | prefixPl_015 | 1117664 | string | i | PL01_ | minChars:2;maxChars:12; spaces:False; lettersNumbersOnly:True; | The configured tag name prefix for the plunger lift application. | ✓ | ✓ | ||||||||||
| Control State Tag Name 15 | controlStateTgNm_015 | 1117665 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Control State' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Inhibit Open Valve Tag Name 15 | inhibitOpenTgNm_015 | 1117666 | string | bool | o | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Inhibit Open Valve' control parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Load Ratio Tag Name 15 | loadRatioTgNm_015 | 1117667 | string | double | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Load Ratio' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Exec Count Tag Name 15 | execCountTgNm_015 | 1117669 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Execution Count' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Enable Well Coordination 16 | enWellCoord_016 | 1117762 | bool | i | False | min:False;max:True; | Whether to include this configuration in the group of plunger lift applications that are coordinated. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Priority Index 16 | priorityIdx_016 | 1117770 | i16 | i | 100 | min:0;max:32767; | Set the priority of this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Remote Well Location 16 | locationRemote_016 | 1117763 | bool | i | False | min:False;max:True; | Set this value when the plunger lift application to be coordinated exists on a different controller or in a different PLC Shift runtime. When set, this application will coordinate the plunger lift application through the use of tags that are mapped through the PLC. When false, this application will coordinate the plunger lift application through an internal mechanism and the application must be in the same PLC Shift runtime. | ✓ | ✓ | ✓ | |||||||||
| Plunger Lift Application Prefix 16 | prefixPl_016 | 1117764 | string | i | PL01_ | minChars:2;maxChars:12; spaces:False; lettersNumbersOnly:True; | The configured tag name prefix for the plunger lift application. | ✓ | ✓ | ||||||||||
| Control State Tag Name 16 | controlStateTgNm_016 | 1117765 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Control State' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Inhibit Open Valve Tag Name 16 | inhibitOpenTgNm_016 | 1117766 | string | bool | o | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Inhibit Open Valve' control parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Load Ratio Tag Name 16 | loadRatioTgNm_016 | 1117767 | string | double | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Load Ratio' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | |||||||
| Exec Count Tag Name 16 | execCountTgNm_016 | 1117769 | string | i32 | i | minChars:0;maxChars:32; spaces:False; lettersNumbersOnly:True; | The tag name of the 'Execution Count' status parameter for the plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ |
Group 'Lift Override'
Control settings to override configured behavior
This is a control group that has 16 parameters.
| Parameter | Tag Name | ID | Value Type | Tag Value Type | IO Type | Default Value | Limits | Default Units | Allowed Units | Description | Sync Enabled | Sync Default | Export Enabled | Publish MQTT Enabled | Subscribe MQTT Enabled | Show in Manager Enabled | Modbus Server Enabled | gRPC Read Enabled | gRPC Write Enabled |
| Override Inhibit 01 | overrideInhibit01 | 8454144 | bool | io | False | min:False;max:True; | Set this value to override this application and force 'Inhibit Open Valve' for 'PL App 01' to 'false'. This allows the well to flow without any coordination. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | |||
| Override Inhibit 02 | overrideInhibit02 | 8454145 | bool | io | False | min:False;max:True; | Set this value to override this application and force 'Inhibit Open Valve' for 'PL App 02' to 'false'. This allows the well to flow without any coordination. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | |||
| Override Inhibit 03 | overrideInhibit03 | 8454146 | bool | io | False | min:False;max:True; | Set this value to override this application and force 'Inhibit Open Valve' for 'PL App 03' to 'false'. This allows the well to flow without any coordination. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | |||
| Override Inhibit 04 | overrideInhibit04 | 8454147 | bool | io | False | min:False;max:True; | Set this value to override this application and force 'Inhibit Open Valve' for 'PL App 04' to 'false'. This allows the well to flow without any coordination. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | |||
| Override Inhibit 05 | overrideInhibit05 | 8454148 | bool | io | False | min:False;max:True; | Set this value to override this application and force 'Inhibit Open Valve' for 'PL App 05' to 'false'. This allows the well to flow without any coordination. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | |||
| Override Inhibit 06 | overrideInhibit06 | 8454149 | bool | io | False | min:False;max:True; | Set this value to override this application and force 'Inhibit Open Valve' for 'PL App 06' to 'false'. This allows the well to flow without any coordination. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | |||
| Override Inhibit 07 | overrideInhibit07 | 8454150 | bool | io | False | min:False;max:True; | Set this value to override this application and force 'Inhibit Open Valve' for 'PL App 07' to 'false'. This allows the well to flow without any coordination. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | |||
| Override Inhibit 08 | overrideInhibit08 | 8454151 | bool | io | False | min:False;max:True; | Set this value to override this application and force 'Inhibit Open Valve' for 'PL App 08' to 'false'. This allows the well to flow without any coordination. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | |||
| Override Inhibit 09 | overrideInhibit09 | 8454152 | bool | io | False | min:False;max:True; | Set this value to override this application and force 'Inhibit Open Valve' for 'PL App 09' to 'false'. This allows the well to flow without any coordination. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | |||
| Override Inhibit 10 | overrideInhibit10 | 8454153 | bool | io | False | min:False;max:True; | Set this value to override this application and force 'Inhibit Open Valve' for 'PL App 10' to 'false'. This allows the well to flow without any coordination. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | |||
| Override Inhibit 11 | overrideInhibit11 | 8454154 | bool | io | False | min:False;max:True; | Set this value to override this application and force 'Inhibit Open Valve' for 'PL App 11' to 'false'. This allows the well to flow without any coordination. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | |||
| Override Inhibit 12 | overrideInhibit12 | 8454155 | bool | io | False | min:False;max:True; | Set this value to override this application and force 'Inhibit Open Valve' for 'PL App 12' to 'false'. This allows the well to flow without any coordination. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | |||
| Override Inhibit 13 | overrideInhibit13 | 8454156 | bool | io | False | min:False;max:True; | Set this value to override this application and force 'Inhibit Open Valve' for 'PL App 13' to 'false'. This allows the well to flow without any coordination. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | |||
| Override Inhibit 14 | overrideInhibit14 | 8454157 | bool | io | False | min:False;max:True; | Set this value to override this application and force 'Inhibit Open Valve' for 'PL App 14' to 'false'. This allows the well to flow without any coordination. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | |||
| Override Inhibit 15 | overrideInhibit15 | 8454158 | bool | io | False | min:False;max:True; | Set this value to override this application and force 'Inhibit Open Valve' for 'PL App 15' to 'false'. This allows the well to flow without any coordination. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | |||
| Override Inhibit 16 | overrideInhibit16 | 8454159 | bool | io | False | min:False;max:True; | Set this value to override this application and force 'Inhibit Open Valve' for 'PL App 16' to 'false'. This allows the well to flow without any coordination. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Group 'Configuration Group Status'
Parameters in this group indicate the status of the associated configuration group
This is a status group that has 1 parameters.
| Parameter | Tag Name | ID | Value Type | Tag Value Type | IO Type | Default Value | Limits | Default Units | Allowed Units | Description | Sync Enabled | Sync Default | Export Enabled | Publish MQTT Enabled | Subscribe MQTT Enabled | Show in Manager Enabled | Modbus Server Enabled | gRPC Read Enabled | gRPC Write Enabled |
| Plunger Coordination Group Configuration Invalid | plCoordGrpVld | 5373952 | bool | o | Indicates whether the configuration of the Plunger Coordination group is valid or invalid. A low value indicates a valid configuration. A high value indicates an invalid configuration | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Group 'Plunger Status'
Status information for plunger lift applications
This is a status group that has 122 parameters.
| Parameter | Tag Name | ID | Value Type | Tag Value Type | IO Type | Default Value | Limits | Default Units | Allowed Units | Description | Sync Enabled | Sync Default | Export Enabled | Publish MQTT Enabled | Subscribe MQTT Enabled | Show in Manager Enabled | Modbus Server Enabled | gRPC Read Enabled | gRPC Write Enabled |
| Lifting Count | liftingCount | 5439488 | i16 | o | The number of wells that are actively lifting. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Inhibit Count | inhibitCount | 5439489 | i16 | o | The number of wells that are prevented from open their sales valve. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Flowing Count | flowingCount | 5439490 | i16 | o | The number of wells where the sales valve is open and the well is flowing. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Coordination Is Enabled 01 | wellCoordEn_001 | 5441639 | bool | o | Whether this application is enabled and included in the coordination group. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Inputs Bad 01 | wellInputsBad_001 | 5441643 | bool | o | Whether the inputs to this well are bad. Bad inputs typically indicate a configuration issue or communication issue with the Lift Manager application and the Plunger Lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Lifting 01 | wellIsLifting_001 | 5441640 | bool | o | Whether this well is actively lifting. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Inhibited 01 | wellIsInhibited_001 | 5441641 | bool | o | Whether this well is prevented from opening its sales valve. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Flowing 01 | wellIsFlowing_001 | 5441642 | bool | o | Whether this well has its sales valve open and is flowing. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Load Ratio 01 | wellLdRatio_001 | 5441644 | double | o | 1:percent; | 1:percent; | The load ratio for this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Well Control State 01 | welCntrlState_001 | 5441645 | i32 | o | 0:Initialize | 0:Initialize; 1:Waiting For Flow; 2:Waiting For Plunger Arrival; 3:After Flow Delay; 4:Waiting to Shut In; 5:After Shut In Delay; 6:Manual Override; 7:Protection Enabled; 8:Paused; 9:End of Cycle; 10:Inhibit Open; | The control state for this plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Coordination Is Enabled 02 | wellCoordEn_002 | 5441739 | bool | o | Whether this application is enabled and included in the coordination group. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Inputs Bad 02 | wellInputsBad_002 | 5441743 | bool | o | Whether the inputs to this well are bad. Bad inputs typically indicate a configuration issue or communication issue with the Lift Manager application and the Plunger Lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Lifting 02 | wellIsLifting_002 | 5441740 | bool | o | Whether this well is actively lifting. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Inhibited 02 | wellIsInhibited_002 | 5441741 | bool | o | Whether this well is prevented from opening its sales valve. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Flowing 02 | wellIsFlowing_002 | 5441742 | bool | o | Whether this well has its sales valve open and is flowing. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Load Ratio 02 | wellLdRatio_002 | 5441744 | double | o | 1:percent; | 1:percent; | The load ratio for this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Well Control State 02 | welCntrlState_002 | 5441745 | i32 | o | 0:Initialize | 0:Initialize; 1:Waiting For Flow; 2:Waiting For Plunger Arrival; 3:After Flow Delay; 4:Waiting to Shut In; 5:After Shut In Delay; 6:Manual Override; 7:Protection Enabled; 8:Paused; 9:End of Cycle; 10:Inhibit Open; | The control state for this plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Coordination Is Enabled 03 | wellCoordEn_003 | 5441839 | bool | o | Whether this application is enabled and included in the coordination group. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Inputs Bad 03 | wellInputsBad_003 | 5441843 | bool | o | Whether the inputs to this well are bad. Bad inputs typically indicate a configuration issue or communication issue with the Lift Manager application and the Plunger Lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Lifting 03 | wellIsLifting_003 | 5441840 | bool | o | Whether this well is actively lifting. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Inhibited 03 | wellIsInhibited_003 | 5441841 | bool | o | Whether this well is prevented from opening its sales valve. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Flowing 03 | wellIsFlowing_003 | 5441842 | bool | o | Whether this well has its sales valve open and is flowing. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Load Ratio 03 | wellLdRatio_003 | 5441844 | double | o | 1:percent; | 1:percent; | The load ratio for this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Well Control State 03 | welCntrlState_003 | 5441845 | i32 | o | 0:Initialize | 0:Initialize; 1:Waiting For Flow; 2:Waiting For Plunger Arrival; 3:After Flow Delay; 4:Waiting to Shut In; 5:After Shut In Delay; 6:Manual Override; 7:Protection Enabled; 8:Paused; 9:End of Cycle; 10:Inhibit Open; | The control state for this plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Coordination Is Enabled 04 | wellCoordEn_004 | 5441939 | bool | o | Whether this application is enabled and included in the coordination group. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Inputs Bad 04 | wellInputsBad_004 | 5441943 | bool | o | Whether the inputs to this well are bad. Bad inputs typically indicate a configuration issue or communication issue with the Lift Manager application and the Plunger Lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Lifting 04 | wellIsLifting_004 | 5441940 | bool | o | Whether this well is actively lifting. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Inhibited 04 | wellIsInhibited_004 | 5441941 | bool | o | Whether this well is prevented from opening its sales valve. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Flowing 04 | wellIsFlowing_004 | 5441942 | bool | o | Whether this well has its sales valve open and is flowing. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Load Ratio 04 | wellLdRatio_004 | 5441944 | double | o | 1:percent; | 1:percent; | The load ratio for this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Well Control State 04 | welCntrlState_004 | 5441945 | i32 | o | 0:Initialize | 0:Initialize; 1:Waiting For Flow; 2:Waiting For Plunger Arrival; 3:After Flow Delay; 4:Waiting to Shut In; 5:After Shut In Delay; 6:Manual Override; 7:Protection Enabled; 8:Paused; 9:End of Cycle; 10:Inhibit Open; | The control state for this plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Coordination Is Enabled 05 | wellCoordEn_005 | 5442039 | bool | o | Whether this application is enabled and included in the coordination group. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Inputs Bad 05 | wellInputsBad_005 | 5442043 | bool | o | Whether the inputs to this well are bad. Bad inputs typically indicate a configuration issue or communication issue with the Lift Manager application and the Plunger Lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Lifting 05 | wellIsLifting_005 | 5442040 | bool | o | Whether this well is actively lifting. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Inhibited 05 | wellIsInhibited_005 | 5442041 | bool | o | Whether this well is prevented from opening its sales valve. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Flowing 05 | wellIsFlowing_005 | 5442042 | bool | o | Whether this well has its sales valve open and is flowing. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Load Ratio 05 | wellLdRatio_005 | 5442044 | double | o | 1:percent; | 1:percent; | The load ratio for this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Well Control State 05 | welCntrlState_005 | 5442045 | i32 | o | 0:Initialize | 0:Initialize; 1:Waiting For Flow; 2:Waiting For Plunger Arrival; 3:After Flow Delay; 4:Waiting to Shut In; 5:After Shut In Delay; 6:Manual Override; 7:Protection Enabled; 8:Paused; 9:End of Cycle; 10:Inhibit Open; | The control state for this plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Coordination Is Enabled 06 | wellCoordEn_006 | 5442139 | bool | o | Whether this application is enabled and included in the coordination group. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Inputs Bad 06 | wellInputsBad_006 | 5442143 | bool | o | Whether the inputs to this well are bad. Bad inputs typically indicate a configuration issue or communication issue with the Lift Manager application and the Plunger Lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Lifting 06 | wellIsLifting_006 | 5442140 | bool | o | Whether this well is actively lifting. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Inhibited 06 | wellIsInhibited_006 | 5442141 | bool | o | Whether this well is prevented from opening its sales valve. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Flowing 06 | wellIsFlowing_006 | 5442142 | bool | o | Whether this well has its sales valve open and is flowing. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Load Ratio 06 | wellLdRatio_006 | 5442144 | double | o | 1:percent; | 1:percent; | The load ratio for this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Well Control State 06 | welCntrlState_006 | 5442145 | i32 | o | 0:Initialize | 0:Initialize; 1:Waiting For Flow; 2:Waiting For Plunger Arrival; 3:After Flow Delay; 4:Waiting to Shut In; 5:After Shut In Delay; 6:Manual Override; 7:Protection Enabled; 8:Paused; 9:End of Cycle; 10:Inhibit Open; | The control state for this plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Coordination Is Enabled 07 | wellCoordEn_007 | 5442239 | bool | o | Whether this application is enabled and included in the coordination group. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Inputs Bad 07 | wellInputsBad_007 | 5442243 | bool | o | Whether the inputs to this well are bad. Bad inputs typically indicate a configuration issue or communication issue with the Lift Manager application and the Plunger Lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Lifting 07 | wellIsLifting_007 | 5442240 | bool | o | Whether this well is actively lifting. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Inhibited 07 | wellIsInhibited_007 | 5442241 | bool | o | Whether this well is prevented from opening its sales valve. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Flowing 07 | wellIsFlowing_007 | 5442242 | bool | o | Whether this well has its sales valve open and is flowing. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Load Ratio 07 | wellLdRatio_007 | 5442244 | double | o | 1:percent; | 1:percent; | The load ratio for this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Well Control State 07 | welCntrlState_007 | 5442245 | i32 | o | 0:Initialize | 0:Initialize; 1:Waiting For Flow; 2:Waiting For Plunger Arrival; 3:After Flow Delay; 4:Waiting to Shut In; 5:After Shut In Delay; 6:Manual Override; 7:Protection Enabled; 8:Paused; 9:End of Cycle; 10:Inhibit Open; | The control state for this plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Coordination Is Enabled 08 | wellCoordEn_008 | 5442339 | bool | o | Whether this application is enabled and included in the coordination group. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Inputs Bad 08 | wellInputsBad_008 | 5442343 | bool | o | Whether the inputs to this well are bad. Bad inputs typically indicate a configuration issue or communication issue with the Lift Manager application and the Plunger Lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Lifting 08 | wellIsLifting_008 | 5442340 | bool | o | Whether this well is actively lifting. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Inhibited 08 | wellIsInhibited_008 | 5442341 | bool | o | Whether this well is prevented from opening its sales valve. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Flowing 08 | wellIsFlowing_008 | 5442342 | bool | o | Whether this well has its sales valve open and is flowing. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Load Ratio 08 | wellLdRatio_008 | 5442344 | double | o | 1:percent; | 1:percent; | The load ratio for this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Well Control State 08 | welCntrlState_008 | 5442345 | i32 | o | 0:Initialize | 0:Initialize; 1:Waiting For Flow; 2:Waiting For Plunger Arrival; 3:After Flow Delay; 4:Waiting to Shut In; 5:After Shut In Delay; 6:Manual Override; 7:Protection Enabled; 8:Paused; 9:End of Cycle; 10:Inhibit Open; | The control state for this plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Coordination Is Enabled 09 | wellCoordEn_009 | 5442439 | bool | o | Whether this application is enabled and included in the coordination group. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Inputs Bad 09 | wellInputsBad_009 | 5442443 | bool | o | Whether the inputs to this well are bad. Bad inputs typically indicate a configuration issue or communication issue with the Lift Manager application and the Plunger Lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Lifting 09 | wellIsLifting_009 | 5442440 | bool | o | Whether this well is actively lifting. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Inhibited 09 | wellIsInhibited_009 | 5442441 | bool | o | Whether this well is prevented from opening its sales valve. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Flowing 09 | wellIsFlowing_009 | 5442442 | bool | o | Whether this well has its sales valve open and is flowing. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Load Ratio 09 | wellLdRatio_009 | 5442444 | double | o | 1:percent; | 1:percent; | The load ratio for this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Well Control State 09 | welCntrlState_009 | 5442445 | i32 | o | 0:Initialize | 0:Initialize; 1:Waiting For Flow; 2:Waiting For Plunger Arrival; 3:After Flow Delay; 4:Waiting to Shut In; 5:After Shut In Delay; 6:Manual Override; 7:Protection Enabled; 8:Paused; 9:End of Cycle; 10:Inhibit Open; | The control state for this plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Coordination Is Enabled 10 | wellCoordEn_010 | 5442539 | bool | o | Whether this application is enabled and included in the coordination group. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Inputs Bad 10 | wellInputsBad_010 | 5442543 | bool | o | Whether the inputs to this well are bad. Bad inputs typically indicate a configuration issue or communication issue with the Lift Manager application and the Plunger Lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Lifting 10 | wellIsLifting_010 | 5442540 | bool | o | Whether this well is actively lifting. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Inhibited 10 | wellIsInhibited_010 | 5442541 | bool | o | Whether this well is prevented from opening its sales valve. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Flowing 10 | wellIsFlowing_010 | 5442542 | bool | o | Whether this well has its sales valve open and is flowing. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Load Ratio 10 | wellLdRatio_010 | 5442544 | double | o | 1:percent; | 1:percent; | The load ratio for this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Well Control State 10 | welCntrlState_010 | 5442545 | i32 | o | 0:Initialize | 0:Initialize; 1:Waiting For Flow; 2:Waiting For Plunger Arrival; 3:After Flow Delay; 4:Waiting to Shut In; 5:After Shut In Delay; 6:Manual Override; 7:Protection Enabled; 8:Paused; 9:End of Cycle; 10:Inhibit Open; | The control state for this plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Coordination Is Enabled 11 | wellCoordEn_011 | 5442639 | bool | o | Whether this application is enabled and included in the coordination group. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Inputs Bad 11 | wellInputsBad_011 | 5442643 | bool | o | Whether the inputs to this well are bad. Bad inputs typically indicate a configuration issue or communication issue with the Lift Manager application and the Plunger Lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Lifting 11 | wellIsLifting_011 | 5442640 | bool | o | Whether this well is actively lifting. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Inhibited 11 | wellIsInhibited_011 | 5442641 | bool | o | Whether this well is prevented from opening its sales valve. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Flowing 11 | wellIsFlowing_011 | 5442642 | bool | o | Whether this well has its sales valve open and is flowing. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Load Ratio 11 | wellLdRatio_011 | 5442644 | double | o | 1:percent; | 1:percent; | The load ratio for this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Well Control State 11 | welCntrlState_011 | 5442645 | i32 | o | 0:Initialize | 0:Initialize; 1:Waiting For Flow; 2:Waiting For Plunger Arrival; 3:After Flow Delay; 4:Waiting to Shut In; 5:After Shut In Delay; 6:Manual Override; 7:Protection Enabled; 8:Paused; 9:End of Cycle; 10:Inhibit Open; | The control state for this plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Coordination Is Enabled 12 | wellCoordEn_012 | 5442739 | bool | o | Whether this application is enabled and included in the coordination group. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Inputs Bad 12 | wellInputsBad_012 | 5442743 | bool | o | Whether the inputs to this well are bad. Bad inputs typically indicate a configuration issue or communication issue with the Lift Manager application and the Plunger Lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Lifting 12 | wellIsLifting_012 | 5442740 | bool | o | Whether this well is actively lifting. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Inhibited 12 | wellIsInhibited_012 | 5442741 | bool | o | Whether this well is prevented from opening its sales valve. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Flowing 12 | wellIsFlowing_012 | 5442742 | bool | o | Whether this well has its sales valve open and is flowing. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Load Ratio 12 | wellLdRatio_012 | 5442744 | double | o | 1:percent; | 1:percent; | The load ratio for this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Well Control State 12 | welCntrlState_012 | 5442745 | i32 | o | 0:Initialize | 0:Initialize; 1:Waiting For Flow; 2:Waiting For Plunger Arrival; 3:After Flow Delay; 4:Waiting to Shut In; 5:After Shut In Delay; 6:Manual Override; 7:Protection Enabled; 8:Paused; 9:End of Cycle; 10:Inhibit Open; | The control state for this plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Coordination Is Enabled 13 | wellCoordEn_013 | 5442839 | bool | o | Whether this application is enabled and included in the coordination group. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Inputs Bad 13 | wellInputsBad_013 | 5442843 | bool | o | Whether the inputs to this well are bad. Bad inputs typically indicate a configuration issue or communication issue with the Lift Manager application and the Plunger Lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Lifting 13 | wellIsLifting_013 | 5442840 | bool | o | Whether this well is actively lifting. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Inhibited 13 | wellIsInhibited_013 | 5442841 | bool | o | Whether this well is prevented from opening its sales valve. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Flowing 13 | wellIsFlowing_013 | 5442842 | bool | o | Whether this well has its sales valve open and is flowing. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Load Ratio 13 | wellLdRatio_013 | 5442844 | double | o | 1:percent; | 1:percent; | The load ratio for this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Well Control State 13 | welCntrlState_013 | 5442845 | i32 | o | 0:Initialize | 0:Initialize; 1:Waiting For Flow; 2:Waiting For Plunger Arrival; 3:After Flow Delay; 4:Waiting to Shut In; 5:After Shut In Delay; 6:Manual Override; 7:Protection Enabled; 8:Paused; 9:End of Cycle; 10:Inhibit Open; | The control state for this plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Coordination Is Enabled 14 | wellCoordEn_014 | 5442939 | bool | o | Whether this application is enabled and included in the coordination group. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Inputs Bad 14 | wellInputsBad_014 | 5442943 | bool | o | Whether the inputs to this well are bad. Bad inputs typically indicate a configuration issue or communication issue with the Lift Manager application and the Plunger Lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Lifting 14 | wellIsLifting_014 | 5442940 | bool | o | Whether this well is actively lifting. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Inhibited 14 | wellIsInhibited_014 | 5442941 | bool | o | Whether this well is prevented from opening its sales valve. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Flowing 14 | wellIsFlowing_014 | 5442942 | bool | o | Whether this well has its sales valve open and is flowing. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Load Ratio 14 | wellLdRatio_014 | 5442944 | double | o | 1:percent; | 1:percent; | The load ratio for this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Well Control State 14 | welCntrlState_014 | 5442945 | i32 | o | 0:Initialize | 0:Initialize; 1:Waiting For Flow; 2:Waiting For Plunger Arrival; 3:After Flow Delay; 4:Waiting to Shut In; 5:After Shut In Delay; 6:Manual Override; 7:Protection Enabled; 8:Paused; 9:End of Cycle; 10:Inhibit Open; | The control state for this plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Coordination Is Enabled 15 | wellCoordEn_015 | 5443039 | bool | o | Whether this application is enabled and included in the coordination group. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Inputs Bad 15 | wellInputsBad_015 | 5443043 | bool | o | Whether the inputs to this well are bad. Bad inputs typically indicate a configuration issue or communication issue with the Lift Manager application and the Plunger Lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Lifting 15 | wellIsLifting_015 | 5443040 | bool | o | Whether this well is actively lifting. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Inhibited 15 | wellIsInhibited_015 | 5443041 | bool | o | Whether this well is prevented from opening its sales valve. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Flowing 15 | wellIsFlowing_015 | 5443042 | bool | o | Whether this well has its sales valve open and is flowing. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Load Ratio 15 | wellLdRatio_015 | 5443044 | double | o | 1:percent; | 1:percent; | The load ratio for this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Well Control State 15 | welCntrlState_015 | 5443045 | i32 | o | 0:Initialize | 0:Initialize; 1:Waiting For Flow; 2:Waiting For Plunger Arrival; 3:After Flow Delay; 4:Waiting to Shut In; 5:After Shut In Delay; 6:Manual Override; 7:Protection Enabled; 8:Paused; 9:End of Cycle; 10:Inhibit Open; | The control state for this plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Coordination Is Enabled 16 | wellCoordEn_016 | 5443139 | bool | o | Whether this application is enabled and included in the coordination group. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Inputs Bad 16 | wellInputsBad_016 | 5443143 | bool | o | Whether the inputs to this well are bad. Bad inputs typically indicate a configuration issue or communication issue with the Lift Manager application and the Plunger Lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Lifting 16 | wellIsLifting_016 | 5443140 | bool | o | Whether this well is actively lifting. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Inhibited 16 | wellIsInhibited_016 | 5443141 | bool | o | Whether this well is prevented from opening its sales valve. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Is Flowing 16 | wellIsFlowing_016 | 5443142 | bool | o | Whether this well has its sales valve open and is flowing. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||||
| Well Load Ratio 16 | wellLdRatio_016 | 5443144 | double | o | 1:percent; | 1:percent; | The load ratio for this well. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ||||
| Well Control State 16 | welCntrlState_016 | 5443145 | i32 | o | 0:Initialize | 0:Initialize; 1:Waiting For Flow; 2:Waiting For Plunger Arrival; 3:After Flow Delay; 4:Waiting to Shut In; 5:After Shut In Delay; 6:Manual Override; 7:Protection Enabled; 8:Paused; 9:End of Cycle; 10:Inhibit Open; | The control state for this plunger lift application. | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |